NPSHA (Available) must be greater than NPSHR (Required) by at least 3-5 feet of head. If your system NPSHA is too thin, the pump will cavitate the moment the system load increases or the suction strainer starts to plug.
Pump Suction Dynamics
Increasing system temperature drastically changes the vapor pressure of the fluid. A pump that runs perfectly at 70°F might start cavitating at 120°F because the vapor pressure threshold has shifted, effectively shrinking the NPSHA margin.
| Margin (Ft) | Risk Level | Required Action |
|---|---|---|
| < 0 | Severe | Stop pump. Cavitation is destroying the impeller. |
| 0 – 3 | Unstable | Address suction restrictions (strainers) or reduce fluid temp. |
| 3+ | Secure | Maintain system monitoring. |
Diagnostic Gateway Challenge
A pump is making a sound like “pumping rocks.” You determine NPSHA is 14ft and NPSHR is 13ft. Why is the pump cavitating despite the margin being technically positive?